Surge Immunity Testing Services

Surge immunity testing evaluates your product's ability to withstand high-energy transients caused by lightning strikes and power system switching. Compatible Electronics provides comprehensive IEC 61000-4-5 surge testing services.

What is Surge Immunity Testing?

Surges are high-energy transients that can occur on AC power lines. See also the related EFT/Burst immunity test for fast transients due to lightning strikes (direct or indirect), switching of large loads, and fault conditions. These events can damage unprotected equipment and are a leading cause of electronic failures.

Our Surge Testing Capabilities

Voltage Levels

  • Up to ±4 kV (line-to-earth)
  • Up to ±2 kV (line-to-line)
  • Both polarities tested

Waveforms

  • 1.2/50 μs voltage waveform
  • 8/20 μs current waveform
  • Combination wave generator (1.2/50 μs - 8/20 μs)

Phase Synchronization

  • 0° phase angle
  • 90° phase angle
  • 180° phase angle
  • 270° phase angle

Standards We Test To

IEC / EN Standards

Product-Specific

Test Configurations

Line-to-earth (L-PE, N-PE) - Common mode
Line-to-line (L-N) - Differential mode
DC power lines
Signal and telecommunications lines
I/O ports (where applicable)

Standard Test Levels

1

Level 1

±0.5 kV line-to-line, ±0.5 kV line-to-earth

2

Level 2

±1 kV line-to-line, ±1 kV line-to-earth

3

Level 3

±2 kV line-to-line, ±2 kV line-to-earth

4

Level 4

±4 kV line-to-earth only

Common Surge Failure Modes

✕

Power supply damage

✕

MOV or TVS device failure

✕

Blown fuses or circuit breakers

✕

PCB trace damage

✕

Component breakdown. Our EMC design consulting team can advise on surge protection strategies.

Accredited Standard Versions & Locations

Compatible Electronics holds NVLAP accreditation for multiple editions of IEC 61000-4-5 including the UK BS EN version and Korean equivalents.

StandardDescriptionLocations
IEC 61000-4-5 Ed. 3.1 (2017)Current edition — referenced by EN 61000-6-1 (2019), EN 61000-6-2 (2019), IEC 60601-1-2 Ed.4. Introduced clarified earth connection and telecom port requirements.Lake Forest
IEC 61000-4-5 Ed. 3.0 (2014)Previous current edition — product standards 2014–2019Lake Forest
IEC 61000-4-5 Ed. 1.1 (2001); EN 61000-4-5Earlier edition — older CE marking and legacy product standardsLake ForestBreaNewbury Park
BS EN 61000-4-5 (2006)British Standard — UK UKCA marking submissions. See UK EMC learning page.Lake Forest
KS C 9610-4-5; KN 61000-4-5Korean equivalents — required for Korean KC/KCC certificationLake ForestBrea
AS IEC 61000.4.5Australian equivalent — required for RCM certificationLake Forest

🔎 For current EU CE marking using EN 61000-6-1:2019 or EN 61000-6-2:2019, Ed. 3.1 (2017) is appropriate. For UK UKCA marking, the BS EN version applies. Read the generic standards learning page for context on applicable versions.